Loading and supporting of the cable trays
The method of supporting are recommended according to load: 2 brackets always placed 0.55 m from the trays ends.
| Maximum permissible load |
| FN603, 1403 | 24 kg/m |
| FN60, 140, 240, 360, 480, 600 | 60 kg/m |
| FN2402, 3602, 4802 | 120 kg/m |
| In case of cutting out the side wires, or in case of other type of supporting, throughs load capacity is reduced. |
| |
| Load capacity of brackets |
| FK1 | 489 N |
| FK2-A | 327 N |
| FK2-B | 1153 N |
| FK3 | 770 N |
| FK4 | 1200 N |
| FK5 | 1027 N |
| Actual load is limited by the strength of a bracket attachment to the wall (load capacity of the wall plugs). |
| |
| Load capacity in case of installation on FD1 holder |
| FN60 / FD1 | 42 kg/m |
| FN140 / FD1 | 30 kg/m |